History of Ductmate
Products
Installations
Distributors
News
Click here to submit your Feedback
Quality Management System Certification
FIRE RESISTANT TAB DOORS
Technical

DUCTMATE FIRE RESISTANT TAB DOORS FOR RECTANGULAR DUCTING

These types of doors meet the requirement of HVCA DW144 specification regarding air leakage criteria. All doors have been tested by BSRIA the approved Test House for HVCA.

Copies of Test Certificates available upon request.

SYSTEM COMPONENTS AND CONSTRUCTION SPECIFICATION

COATING FFC 1 Intumescent
COLOUR RAL2001 (Orange Brown)
PANELS Galvanised Steel BS EN10142: +A1 1995
DOOR GASKET Ceramic Fibre
FRAME GASKET FFC Intumescent Tape
INSULATION Cafco TD Board (155 Kg/m3)
RIVET TYPE Steel Rivet

WEIGHTS FOR INDIVIDUAL DOORS (GALV.)

DIMS.
WEIGHT EACH (KG)
DIMS.
WEIGHT
EACH (KG)
DIMS
WEIGHT
EACH (KG)
250 x 125mm
0.92
300 x 200mm
1.23
450 x 450mm
3.79
250 x 250mm
1.24
400 x 300mm
2.06
600 x 400mm
4.53

HEALTH AND SAFETY

Due to the inert nature of Ductmate component parts we consider the product represents no danger to health.

Specific manufacturing and installation Health and Safety issues are dealt with on the appropriate data sheets relating to these products.

Top of the page

Click here to access the Ductmate Online Store